§6313. Standards — Inbound Citations

42 U.S.C. § 6313

Cited by 45 provisions in release 119-102.

Citations to 42 U.S.C. § 6313 as a whole

Citations to §6313(a)

Citations to §6313(a)(5)

Citations to §6313(a)(5)(A)

Citations to §6313(a)(5)(B)

Citations to §6313(a)(5)(C)

Citations to §6313(a)(6)

Citations to §6313(a)(6)(B)

Citations to §6313(a)(9)

Citations to §6313(b)

Citations to §6313(c)

Citations to §6313(c)(4)

Citations to §6313(c)(5)

  • (A) If the Secretary does not issue a final rule for a specific type of commercial refrigerator, freezer, or refrigerator-freezer within the time frame specified in section 6313(c)(5)2 of this title, subsections (b) and (c) of section 6297 of this title shall not apply to that specific type of refrigerator, freezer, or refrigerator-freezer for the period beginning on the date that is 2 years after the scheduled date for a final rule and ending on the date on which the Secretary publishes a final rule covering the specific type of refrigerator, freezer, or refrigerator-freezer.

Citations to §6313(d)

Citations to §6313(d)(1)

Citations to §6313(d)(2)

Citations to §6313(e)(2)

Citations to §6313(f)

Citations to §6313(f)(2)

  • (1) Subject to paragraphs (2) through (6), each walk-in cooler or walk-in freezer manufactured on or after January 1, 2009, shall—
    (A) have automatic door closers that firmly close all walk-in doors that have been closed to within 1 inch of full closure, except that this subparagraph shall not apply to doors wider than 3 feet 9 inches or taller than 7 feet;
    (B) have strip doors, spring hinged doors, or other method of minimizing infiltration when doors are open;
    (C) contain wall, ceiling, and door insulation of at least R–25 for coolers and R–32 for freezers, except that this subparagraph shall not apply to glazed portions of doors nor to structural members;
    (D) contain floor insulation of at least R–28 for freezers;
    (E) for evaporator fan motors of under 1 horsepower and less than 460 volts, use—
    (i) electronically commutated motors (brushless direct current motors); or
    (ii) 3-phase motors;
    (F) for condenser fan motors of under 1 horsepower, use—
    (i) electronically commutated motors;
    (ii) permanent split capacitor-type motors; or
    (iii) 3-phase motors; and
    (G) for all interior lights, use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any), except that light sources with an efficacy of 40 lumens per watt or less, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.

Citations to §6313(f)(3)

  • (1) Subject to paragraphs (2) through (6), each walk-in cooler or walk-in freezer manufactured on or after January 1, 2009, shall—
    (A) have automatic door closers that firmly close all walk-in doors that have been closed to within 1 inch of full closure, except that this subparagraph shall not apply to doors wider than 3 feet 9 inches or taller than 7 feet;
    (B) have strip doors, spring hinged doors, or other method of minimizing infiltration when doors are open;
    (C) contain wall, ceiling, and door insulation of at least R–25 for coolers and R–32 for freezers, except that this subparagraph shall not apply to glazed portions of doors nor to structural members;
    (D) contain floor insulation of at least R–28 for freezers;
    (E) for evaporator fan motors of under 1 horsepower and less than 460 volts, use—
    (i) electronically commutated motors (brushless direct current motors); or
    (ii) 3-phase motors;
    (F) for condenser fan motors of under 1 horsepower, use—
    (i) electronically commutated motors;
    (ii) permanent split capacitor-type motors; or
    (iii) 3-phase motors; and
    (G) for all interior lights, use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any), except that light sources with an efficacy of 40 lumens per watt or less, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.

Citations to §6313(f)(4)

  • (1) Subject to paragraphs (2) through (6), each walk-in cooler or walk-in freezer manufactured on or after January 1, 2009, shall—
    (A) have automatic door closers that firmly close all walk-in doors that have been closed to within 1 inch of full closure, except that this subparagraph shall not apply to doors wider than 3 feet 9 inches or taller than 7 feet;
    (B) have strip doors, spring hinged doors, or other method of minimizing infiltration when doors are open;
    (C) contain wall, ceiling, and door insulation of at least R–25 for coolers and R–32 for freezers, except that this subparagraph shall not apply to glazed portions of doors nor to structural members;
    (D) contain floor insulation of at least R–28 for freezers;
    (E) for evaporator fan motors of under 1 horsepower and less than 460 volts, use—
    (i) electronically commutated motors (brushless direct current motors); or
    (ii) 3-phase motors;
    (F) for condenser fan motors of under 1 horsepower, use—
    (i) electronically commutated motors;
    (ii) permanent split capacitor-type motors; or
    (iii) 3-phase motors; and
    (G) for all interior lights, use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any), except that light sources with an efficacy of 40 lumens per watt or less, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.
  • (3) Any standard issued in the State of California before January 1, 2011, under title 20 of the California Code of Regulations, that refers to walk-in coolers and walk-in freezers, for which standards have been established under paragraphs (1), (2), and (3) of section 6313(f) of this title, shall not be preempted until the standards established under section 6313(f)(4) of this title take effect.

Citations to §6313(f)(5)

  • (1) Subject to paragraphs (2) through (6), each walk-in cooler or walk-in freezer manufactured on or after January 1, 2009, shall—
    (A) have automatic door closers that firmly close all walk-in doors that have been closed to within 1 inch of full closure, except that this subparagraph shall not apply to doors wider than 3 feet 9 inches or taller than 7 feet;
    (B) have strip doors, spring hinged doors, or other method of minimizing infiltration when doors are open;
    (C) contain wall, ceiling, and door insulation of at least R–25 for coolers and R–32 for freezers, except that this subparagraph shall not apply to glazed portions of doors nor to structural members;
    (D) contain floor insulation of at least R–28 for freezers;
    (E) for evaporator fan motors of under 1 horsepower and less than 460 volts, use—
    (i) electronically commutated motors (brushless direct current motors); or
    (ii) 3-phase motors;
    (F) for condenser fan motors of under 1 horsepower, use—
    (i) electronically commutated motors;
    (ii) permanent split capacitor-type motors; or
    (iii) 3-phase motors; and
    (G) for all interior lights, use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any), except that light sources with an efficacy of 40 lumens per watt or less, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.

Citations to §6313(f)(6)

  • (1) Subject to paragraphs (2) through (6), each walk-in cooler or walk-in freezer manufactured on or after January 1, 2009, shall—
    (A) have automatic door closers that firmly close all walk-in doors that have been closed to within 1 inch of full closure, except that this subparagraph shall not apply to doors wider than 3 feet 9 inches or taller than 7 feet;
    (B) have strip doors, spring hinged doors, or other method of minimizing infiltration when doors are open;
    (C) contain wall, ceiling, and door insulation of at least R–25 for coolers and R–32 for freezers, except that this subparagraph shall not apply to glazed portions of doors nor to structural members;
    (D) contain floor insulation of at least R–28 for freezers;
    (E) for evaporator fan motors of under 1 horsepower and less than 460 volts, use—
    (i) electronically commutated motors (brushless direct current motors); or
    (ii) 3-phase motors;
    (F) for condenser fan motors of under 1 horsepower, use—
    (i) electronically commutated motors;
    (ii) permanent split capacitor-type motors; or
    (iii) 3-phase motors; and
    (G) for all interior lights, use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any), except that light sources with an efficacy of 40 lumens per watt or less, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.